
Hotel OPL Ozone Engineering Platform
On-premise laundry engineering for hospitality washer demand, dissolved ozone performance and operating maintenance.
Validate the Hotel OPL operating point
Hotel OPL operating condition
Every editable value recalculates the selected operating point immediately.
Hydraulic sizing and capacity
Transparent engineering sequence
8.0 L/min × 1 × 60 = 480 LPH
480 LPH × 0.30 mg/L = 144.0 mg/h
144.0 ÷ 80.0% = 180.0 mg/h
200 − 180.0 = 20.0 mg/h
Effective MTE = WDS 80% product parameter × pressure factor 1.00 × temperature factor 1.00 × water-quality factor 1.00. Maximum target flow = min(2,300 LPH rated flow, 533 LPH ozone-limited flow).
Stage concentration and decay
Each stage receives fresh ozonated water, follows an independent decay profile, and resets to zero at drain. Exposure values are engineering information, not acceptance criteria.
Actual dissolved ozone and BES Design Standard
Ozone exposure continues through wet contact while the generator is OFF. Drain resets concentration before the next stage.
Below BES Design StandardReference operating ranges
Indicative ranges from the supplied BES ROI Annex guidance. These are expected operational benefits, not project-specific ROI calculations or guaranteed savings.
Fill-only generator duty
The generator clock advances only while an inlet valve is open. Wash, soak and agitation contact time never adds EOG runtime.
